Description
The early break contact is a single-pole auxiliary contact that signals the position of the rotary handle in Compact NSX 100/160/250 and PowerPact Multistandard H/J circuit breakers. This contact, in conjunction with a rotary handle and an early make contact (CAM), can anticipate device opening. The auxiliary contact is a changeover type with one normally open and one normally closed contact. Rated at 6A and requiring a minimum load of 100mA at 24VDC, it’s suitable for AC12/AC15/DC12/DC14 utilization categories. Compact NSX and PowerPact chassis can accommodate one early break contact. The device adheres to IEC 60947-5-1 standards.
Specifications
The early break contact is a single-pole auxiliary contact designed for Compact NSX 100/160/250 and PowerPact H/J circuit breakers. It signals the position of the rotary handle, anticipating device opening. This standard auxiliary contact is suitable for drawout mounting and offers a rated current of 6A with a minimum load of 100mA at 24VDC. It complies with a wide range of utilization categories, including AC-12, AC-15, DC-12, and DC-14.